Separation of High Hazard Occupancies Calculator

Separation of Occupancies Having High Hazards Calculator

Looks up required fire-resistance separation ratings (hours) for areas containing high-hazard contents per NFPA 5000 (2024) and NFPA 400 (2025).

Unit system
Applies to room area inputs used for the Protection Level 3 footnote check.

Inputs

Standard / Table reference
Based on NFPA 5000 (2024) — Table 34.3.2.3 and NFPA 400 (2025) — Table 6.2.1.3
Scenario
What are you separating?
ft²
Only used to evaluate the PL3 (*) minimum 2-hour separation note when applicable.
Assumptions & Applicability
  • This calculator performs a table lookup of required fire-resistance separation rating (hours) for areas containing high-hazard contents, based on the referenced standards.
  • You must correctly determine (a) the adjacent occupancy classification and (b) the applicable Protection Level(s) per the applicable standard. This tool does not classify occupancy or protection level.
  • “NP” means the arrangement is not permitted by the referenced table; consult the full code context and the authority having jurisdiction for compliant alternatives.
  • The Protection Level 3 (*) footnote is implemented as a minimum 2-hour separation when the base table requirement is 1 hour and the room is > 150 ft² (≈ 14 m²) storing flammable liquids, combustible liquids, or Class III oxidizers.
  • This tool does not address details such as continuity of barriers, opening protectives, penetrations, duct dampers, shafts, or other code provisions that can affect compliance.
  • Where the standard states that these separation requirements are not reduced based on fire protection system installations, this calculator does not apply any sprinkler-based reductions.
References
  • NFPA 5000 (2024): Separation of occupancies having high hazards — Table 34.3.2.3.
  • NFPA 400 (2025): Separation of occupancies having high hazards — Table 6.2.1.3.
  • Protection Level 3 (*) note implemented: rooms > 150 ft² (≈ 14 m²) storing flammable liquids, combustible liquids, or Class III oxidizers require not less than a 2-hour separation (applied when it changes the outcome).

Sponsored

Contact us regarding this advertising space.